Summary:
Use (and misuse) of "voltage testers" With
trilingual summary
Servicing electrical equipment or
diagnosing system problems usually requires deenergizing the circuit
involved. Sometimes, however, the electrician must work directly on
or near energized circuits. In any event, a technician needs some
simple means of safely determining which terminals or conductors are
energized (and therefore dangerous) and which are not.
Several types of <I>voltage detector<P>
serve that purpose. The oldest, and one of the simplest, is the
solenoid version. When the user places its two leads across a
voltage source, the solenoid magnetically moves a pointer on a scale
to indicate the presence of voltage and its approximate magnitude.
Other visual or audible alarm signals may be provided. Voltmeter
accuracy is not required.
That device has some disadvantages. One
is that it is inductive. Removing the leads from an energized
circuit causes a slight arc, creating a voltage transient that can
disturb sensitive electronic apparatus on the circuit. Also, simply
making that contact runs the risk of an accidental short-circuit.
Other types of detector require no
direct contact with the circuit being tested. Some of them respond
electromagnetically (by induction) to current flow through a
conductor when the detector is placed nearby. An obvious problem is
that conductors can be energized at a dangerous voltage even if no
current is flowing. Another detector design involves capacitive
coupling to the circuit under test, responding to the electrostatic
field surrounding an energized conductor even when no current flows.
Such instruments are useful only for
a-c circuits. Others contain Hall Effect sensors, allowing
non-contact evaluation of d-c voltages.
Associated with each non-contact
detector design is a working range (some instruments provide
multiple ranges for user selection), typically with a minimum or
threshhold level of response. One difficulty with any such detector
is in checking grouped or bundled conductors, some of which may be
energized while others are not. This emphasizes the electrician's
need to understand the limitations of whatever type of voltage
detector is used.
From
"Use (and misuse) of 'voltage testers'" ...by
Richard L. Nailen, EA Engineering Editor -
published in Electrical Apparatus May 2004
© 2004
Barks Publications, Inc. All Rights Reserved.
|