Barks Publications, Inc. Barks Publications, Inc.

                     Home | Electrical Apparatus | ElectroMechanical Bench Reference | Barks Books     

       
 

Electrical Apparatus
The Magazine of Electrical &
Electronic Application & Maintenance


Current Issue Table of Contents
About Electrical Apparatus
Subscription Information
Advertising Information
Staff

   
 

August 2005 featured article


Electrical Apparatus -August 2005

"Power factor: Indicator of Insulation Integrity"

From Electrical Apparatus'  August 2005 issue ...

By Richard L. Nailen, EA Engineering Editor


Order copies of this issue
Subscribe to Electrical Apparatus
About Electrical Apparatus


We welcome your comments and inquiries re: subscriptions and advertising. Please include your name and contact information. Below is a summary of the featured article.   A trilingual summary is published in the magazine in German, French and Spanish.

   

 

 


   

Summary: "Power factor: Indicator of Insulation Integrity"

With trilingual summary

Evaluating the integrity of a motor or generator Insulation system requires several different tests. The effects of moisture or chemical contamination; the quality of an impregnation process; and the presence of air voids within the insulation wall must all be accounted for.

The test most indicative of voids involves measurement of the insulation power factor -- the ratio between capacitance and resistance within the material. Names for the procedure include "power factor," "tangent delta" (abbreviated "tan delta"), "tip-up," or "dielectric loss" test.

A Schering bridge is the instrument used. Because the a-c test voltage used need not exceed the insulation system rating, the test is considered non-destructive. The test voltage causes leakage current to flow through the insulation. As that voltage is increased from an initially low value, electrical discharges occur within the voids, causing the power factor (indicative of the phase separation between resistance and capacitance components of the insulation) to increase (the "tip-up"). Quality of the insulation is judged by the amount of that change.

The true power factor angle "theta" is large, approaching 90 degrees, because for insulation in good condition the resistive component will be quite small. Most easily measured is the complement of that angle, or 90 degrees minus theta -- a small angle delta. The bridge circuit responds to the tangent of delta. For such a small angle, the tangent very nearly equals the sine, which is the same as the cosine of theta (the power factor). Hence, the "tan delta" becomes the test criterion, and its increase with voltage is called the "delta" (increase of) tan delta.

A power factor test is particularly valuable in determining continuity of the semi-conducting surface coating on coils at the higher voltage ratings (above 6.6 kV). For that reason, and because at higher voltages the insulation is more likely to contain internal voids, the power factor test is most often used for rated voltages of 11 kV and higher.

An IEEE standard (No. 286) and the IEC standard (60894) each describe the test method and offer some guidance for interpreting results.

From  "Power factor: Indicator of Insulation Integrity"  ...by Richard L. Nailen, EA Engineering Editor  -published in Electrical Apparatus August 2005 Visit our online webstore to order a copy. © 2005 Barks Publications, Inc.  All Rights Reserved.


Barks Publications, Inc.
400 N. Michigan Ave., Suite 900
Chicago IL 60611-4104

Phone: (312) 321-9440
Fax: (312) 321-1288


E-mail: info@barks.com
Please include your name and contact information.

Contents of this site  Copyright 2000-2008 by Barks Publications, Inc.